- Product Series
Product Series
- product manual
Overview
FL2-0.66II series current transformer, the shell is made of flame retardant, temperature 140 ℃ polycarbonate injection molding, the core is made of oriented cold-rolled silicon steel strip, the secondary wire with high-strength electromagnetic enameled wire, product structure Novel, handsome in appearance, easy installation, small size, large capacity.
Products meet the international GB20840.2-2014.
2 technical indicators
◆ Measurement CT primary current 5 ~ 6300A secondary current 5A, 1A
Protection CT primary current 200 ~ 6300A, secondary current 5A, 1A
Residual current CT primary current 0 ~ 5A, secondary output voltage 1V
Double winding CT primary current 5 ~ 6300A, secondary current 5A
◆ rated working voltage AC0.66kV (equivalent AC0.69kV, GB156-2003)
◆ Rated frequency 50 ~ 60Hz
◆ ambient temperature -30 ℃ ~ 70 ℃ maximum temperature of 120 ℃
◆ altitude ≤ 3000m
◆ frequency withstand voltage 3000V / 1min 50Hz
◆ for the direct invasion without rain, no serious pollution and severe vibration of the place
3 selection instructions
According to a current and bus cross-section and other parameters to select the corresponding specifications products. One wire crosses the transformer window. Remove the top of the transformer wiring cover, remove the lead gasket, the second lead after the shell reset. Metering energy can be used with fixed bolts and hood on the hole sealed seal to prevent theft.
modelmain feature
Remarks
FL2-0.66II
Applicable to multiple busbars (2-6) or multiple cable traversal
Applicable to a wide range of specifications and more
Size
specificationDimensions(mm)
Bore mounting dimensions(mm)
length
width
height
length
height
FL2-0.66 30II
65
44
98
33
31
FL2-0.66 40II
78
46
104
42
31
FL2-0.66 50II
87
46
106
52
31
FL2-0.66 60II
102
48
111
62
32
FL2-0.66 80II
122
47
117
82
32
FL2-0.66 100II
140
50
122
102
32
FL2-0.66 120II
168
48
153
122
52
FL2-0.66 130×60II
178
48
159
132
62
FL2-0.66 60×50II
112
68
142
62
54
FL2-0.66 80×50II
132
68
150
82
54
FL2-0.66 100×50II
152
68
150
102
54
FL2-0.66 30I
60
37
79
32
20
Installation dimensions